DC Electrical Properties

  • Maximum Input Current 48A (208V)
    50A (480V)
    50A (600V)
  • Start Voltage 230V (208V)
    200V (480V)
    200V (600V)
  • Max DC Input Voltage 520V
  • Peak Power Tracking Voltage 220V - 470V (208V)
    250V - 470V (480V)
    250V - 470V (600V)
  • Number of MPPTs 2
  • MPPTs Can Be Paralleled Yes
  • Maximum Current per MPPT 29A
  • Operating Voltage Range 200V - 520V
  • Polarity of Ground Either
  • DC Disconnect Yes
  • Number of String Inputs 6
  • Includes Fuses for String Inputs No
  • Max Rating for String Fuses 15A
  • Rating of Included String Fuses not applicable
  • DC Input Wire Gauge Range 6 AWG – 6 AWG
  • Integrated DC Arc Fault Protection No

AC Electrical Properties

  • Rated Power Output 10000W (208V)
    12000W (480V)
    12000W (600V)
  • Compatible Utility Voltages 208V, 480V, 600V
  • Peak Efficiency 96.5% (208V)
    97.3% (480V)
    97.3% (600V)
  • Weighted Efficiency 96% (208V)
    97% (480V)
    97% (600V)
  • Maximum Output Current 30A (208V)
    16A (480V)
    12.8A (600V)
  • Max OCPD rating data not available
  • AC Disconnect Yes
  • AC Input Wire Gauge Range 10 AWG – 6 AWG
  • Sleep Consumption data not available
  • Standby Consumption 8W

Mechanical Characteristics

  • Height 37.7in (958mm)
  • Width 25.4in (645mm)
  • Depth 8.7in (222mm)
  • Weight 114lb (51.7kg)
  • CSI-Approved Built-in Meter No
  • NEMA Enclosure Rating NEMA 4
  • Cooling Method Natural Convection

Environmental Constraints

  • Ambient Temperature Range -13°F - 140°F (-25°C - 60°C)

Warranties and Compliances